Do you have questions? Our community may have already answered them!
Connect with others in our support forum.
Kinco RP20 temperature expansion for AK8x0M PLC and RP20 bus coupler
- Pt100, Pt1000, Cu50, Cu100
- Thermocouple J, K, E, S, T
- 24 bit, 0.1 °C resolution
- Wire break and limit alarm
- Galvanically isolated
€115.20*
In stock
Lieferzeit: 3 bis 5 TageCustomers also bought
Customers also viewed
You want to measure temperatures directly with sensors, without transmitters in between? The RP20 temperature modules measure on 4 channels with 24 bits and 0.1 °C resolution, either with resistance thermometers or thermocouples. They plug directly onto the Kinco AK840M or onto an RP20 bus coupler.
🏭 Typical Applications
Process ovens and heating zones: Thermocouples type J, K, S or T directly on the module, cold junction compensated internally or externally.
Cooling and air-conditioning: Pt100 and Pt1000 sensors in two- or three-wire connection.
Machine monitoring: Capture bearing, motor and oil temperatures and evaluate limits.
Decentralised measuring points: Together with the EtherCAT or CANopen coupler right at the plant.
🧩 Variants
RP20-0400RD: 4 inputs for resistance thermometers: Pt100, Pt1000, Cu50, Cu100, two- or three-wire connection.
RP20-0400TC: 4 inputs for thermocouples type J, K, E, S, T and mV signals, two-wire; cold junction compensation internal or external.
🖥️ Key Technical Specs
Resolution: 24 bits, temperature resolution 0.1 °C.
Accuracy: ±0.2 % F.S.; for thermocouples this is the accuracy of the A/D converter, the measuring accuracy also depends on the cold junction.
Conversion rate: approx. 1 measurement per second per channel; averaging filter selectable.
Diagnostics: limit and wire break alarm, red LED per channel when a limit is exceeded.
Isolation: galvanically isolated.
🔗 Compatibility
The modules plug directly onto the side of the Kinco AK840M or onto an RP20 bus coupler: RP20C-ECT for EtherCAT, RP20C-CAN for CANopen. Up to 16 modules per station, configured in CODESYS (IEC 61131-3).
Digital: RP20 digital modules: 8 or 16 channels, transistor or relay.
Analogue: RP20 analogue modules: current and voltage signals.
⚠️ Good to Know
Cold junction with thermocouples: The internal compensation needs 30 to 45 minutes to settle and then has an error of up to 6 °C, depending on the heat of the neighbouring modules. For accurate measurements you connect an external Pt100 as cold junction, which achieves up to 0.5 °C. Place modules with little heat next to the RP20-0400TC, not couplers, RP20-PW or output modules.
Designed for slow variables: With approx. one measurement per second per channel, the modules suit temperatures, not fast signals. For those, use the analogue modules with 50 conversions/s.
Plan the bus current: Each module draws 160 mA from the internal K-BUS. An RP20 bus coupler supplies 2.0 A (1.6 A at 55 °C), the AK8X0 1.5 A. If the total is not sufficient, add an RP20-PW power supply module to the station.
No hot swap: Only plug in or remove modules with the power switched off.
🏷️ Manufacturer and Standards
Kinco Automation develops PLCs, HMIs and drive technology. The RP20 modules are CE certified according to EN IEC 61000-6-2:2019 and EN IEC 61000-6-4:2019, EMC immunity according to IEC 61131-2, zone B. Operation −20 °C to +55 °C, storage −40 °C to +70 °C, 10 to 95 % relative humidity non-condensing, IP20.
🔧 Mounting and Scope of Delivery
Mounting: 35 mm DIN rail; the modules snap onto their neighbour sideways via upper and lower guides.
Dimensions: 12 × 100 × 80 mm (W × H × D), approx. 70 g, passive cooling.
Scope of delivery: one module of the selected variant.
Technical Specifications