Solidot PN5R – Support, Wiring Diagram & Commissioning

Interaktiver Anschlussplan Solidot PN5R

Everything for your Solidot PN5R after purchase – for all four models in the Shop: PN5R-3200, -1616B, -1616B+ and -0032B:

  • Interactive wiring diagram: system and field supply, 3-wire sensors and push buttons, loads, COM for NPN/PNP, PROFINET to the controller and daisy chain via the built-in switch, with cable cross-sections and parameters

  • PROFINET: GSDML file, device name and the address of every channel in TIA Portal for your model

  • First steps: commissioning in ten steps, from mounting to the first signal in TIA Portal

  • Dimensions & mounting: outside dimensions, DIN rail or wall mounting with drilling template, minimum clearances and connectors

  • Downloads: user manual, GSDML files, 2D and 3D drawings (also with dust cover) and EPLAN macros

  • Free support from spstiger if you get stuck

Further down:HelpDownloads

Interactive wiring diagram

Tap a terminal or wire in the drawing to see details.

Terminal overview PN5R

TerminalGroupmm²Function
24VSupply0.2–0.75System supply +24 V DC (20.4–28.8 V) for the module electronics, ≤ 50 mA.
0VSupply0.2–0.750 V of the system supply.
IO+Supply0.2–0.75Field supply +24 V DC (IO+), second terminal; internally connected to terminal 3.
IO+Supply0.2–0.75Field supply +24 V DC (IO+), max. 8 A per group. Supplies all 24 V terminals (2) of the channels.
IO−Supply0.2–0.750 V of the field supply (IO−). Internally connected to all 0 V terminals (3) of the channels.
IO−Supply0.2–0.750 V of the field supply (IO−), second terminal; internally connected to terminal 4.
NCSupply0.2–0.75Not connected.
PESupply0.2–0.75Earth. Connect PE securely to earth (manual ch. 6.2).
X1PROFINET–PROFINET IO, 100 Mbit/s, RJ45, cycle time from 1 ms. Both sockets are connected to the built-in switch: one to the controller, the other to the next device. Cable Cat. 5 or higher, shielded (STP) recommended, max. 100 m. Status LED L/A0.
X2PROFINET–PROFINET IO, 100 Mbit/s, RJ45, cycle time from 1 ms. Both sockets are connected to the built-in switch: one to the controller, the other to the next device. Cable Cat. 5 or higher, shielded (STP) recommended, max. 100 m. Status LED L/A1.
1Channel 000.3–1.5Digital input X00, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 0, bit 0 (in TIA Portal %I<start address + 0>.0), 2 bytes higher in the alarm version.
2Channel 000.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 000.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 010.3–1.5Digital input X01, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 0, bit 1 (in TIA Portal %I<start address + 0>.1), 2 bytes higher in the alarm version.
2Channel 010.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 010.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 020.3–1.5Digital input X02, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 0, bit 2 (in TIA Portal %I<start address + 0>.2), 2 bytes higher in the alarm version.
2Channel 020.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 020.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 030.3–1.5Digital input X03, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 0, bit 3 (in TIA Portal %I<start address + 0>.3), 2 bytes higher in the alarm version.
2Channel 030.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 030.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 040.3–1.5Digital input X04, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 0, bit 4 (in TIA Portal %I<start address + 0>.4), 2 bytes higher in the alarm version.
2Channel 040.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 040.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 050.3–1.5Digital input X05, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 0, bit 5 (in TIA Portal %I<start address + 0>.5), 2 bytes higher in the alarm version.
2Channel 050.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 050.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 060.3–1.5Digital input X06, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 0, bit 6 (in TIA Portal %I<start address + 0>.6), 2 bytes higher in the alarm version.
2Channel 060.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 060.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 070.3–1.5Digital input X07, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 0, bit 7 (in TIA Portal %I<start address + 0>.7), 2 bytes higher in the alarm version.
2Channel 070.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 070.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 080.3–1.5Digital input X08, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 1, bit 0 (in TIA Portal %I<start address + 1>.0), 2 bytes higher in the alarm version.
2Channel 080.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 080.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 090.3–1.5Digital input X09, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 1, bit 1 (in TIA Portal %I<start address + 1>.1), 2 bytes higher in the alarm version.
2Channel 090.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 090.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 0A0.3–1.5Digital input X0A, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 1, bit 2 (in TIA Portal %I<start address + 1>.2), 2 bytes higher in the alarm version.
2Channel 0A0.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 0A0.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 0B0.3–1.5Digital input X0B, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 1, bit 3 (in TIA Portal %I<start address + 1>.3), 2 bytes higher in the alarm version.
2Channel 0B0.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 0B0.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 0C0.3–1.5Digital input X0C, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 1, bit 4 (in TIA Portal %I<start address + 1>.4), 2 bytes higher in the alarm version.
2Channel 0C0.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 0C0.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 0D0.3–1.5Digital input X0D, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 1, bit 5 (in TIA Portal %I<start address + 1>.5), 2 bytes higher in the alarm version.
2Channel 0D0.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 0D0.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 0E0.3–1.5Digital input X0E, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 1, bit 6 (in TIA Portal %I<start address + 1>.6), 2 bytes higher in the alarm version.
2Channel 0E0.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 0E0.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 0F0.3–1.5Digital input X0F, PNP: “1” at 15–30 V (≥ 2.1 mA), “0” at −3…+5 V, 4 mA at 24 V, filter adjustable (factory default 3 ms). PROFINET: input byte 1, bit 7 (in TIA Portal %I<start address + 1>.7), 2 bytes higher in the alarm version.
2Channel 0F0.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 0F0.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 000.3–1.5Configurable channel 00 (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 0, bit 0 (in TIA Portal %Q<start address + 0>.0); as input input byte 2, bit 0 (derived), 2 bytes higher in the alarm version.
2Channel 000.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 000.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 010.3–1.5Configurable channel 01 (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 0, bit 1 (in TIA Portal %Q<start address + 0>.1); as input input byte 2, bit 1 (derived), 2 bytes higher in the alarm version.
2Channel 010.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 010.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 020.3–1.5Configurable channel 02 (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 0, bit 2 (in TIA Portal %Q<start address + 0>.2); as input input byte 2, bit 2 (derived), 2 bytes higher in the alarm version.
2Channel 020.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 020.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 030.3–1.5Configurable channel 03 (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 0, bit 3 (in TIA Portal %Q<start address + 0>.3); as input input byte 2, bit 3 (derived), 2 bytes higher in the alarm version.
2Channel 030.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 030.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 040.3–1.5Configurable channel 04 (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 0, bit 4 (in TIA Portal %Q<start address + 0>.4); as input input byte 2, bit 4 (derived), 2 bytes higher in the alarm version.
2Channel 040.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 040.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 050.3–1.5Configurable channel 05 (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 0, bit 5 (in TIA Portal %Q<start address + 0>.5); as input input byte 2, bit 5 (derived), 2 bytes higher in the alarm version.
2Channel 050.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 050.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 060.3–1.5Configurable channel 06 (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 0, bit 6 (in TIA Portal %Q<start address + 0>.6); as input input byte 2, bit 6 (derived), 2 bytes higher in the alarm version.
2Channel 060.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 060.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 070.3–1.5Configurable channel 07 (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 0, bit 7 (in TIA Portal %Q<start address + 0>.7); as input input byte 2, bit 7 (derived), 2 bytes higher in the alarm version.
2Channel 070.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 070.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 080.3–1.5Configurable channel 08 (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 1, bit 0 (in TIA Portal %Q<start address + 1>.0); as input input byte 3, bit 0 (derived), 2 bytes higher in the alarm version.
2Channel 080.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 080.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 090.3–1.5Configurable channel 09 (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 1, bit 1 (in TIA Portal %Q<start address + 1>.1); as input input byte 3, bit 1 (derived), 2 bytes higher in the alarm version.
2Channel 090.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 090.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 0A0.3–1.5Configurable channel 0A (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 1, bit 2 (in TIA Portal %Q<start address + 1>.2); as input input byte 3, bit 2 (derived), 2 bytes higher in the alarm version.
2Channel 0A0.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 0A0.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 0B0.3–1.5Configurable channel 0B (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 1, bit 3 (in TIA Portal %Q<start address + 1>.3); as input input byte 3, bit 3 (derived), 2 bytes higher in the alarm version.
2Channel 0B0.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 0B0.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 0C0.3–1.5Configurable channel 0C (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 1, bit 4 (in TIA Portal %Q<start address + 1>.4); as input input byte 3, bit 4 (derived), 2 bytes higher in the alarm version.
2Channel 0C0.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 0C0.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 0D0.3–1.5Configurable channel 0D (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 1, bit 5 (in TIA Portal %Q<start address + 1>.5); as input input byte 3, bit 5 (derived), 2 bytes higher in the alarm version.
2Channel 0D0.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 0D0.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 0E0.3–1.5Configurable channel 0E (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 1, bit 6 (in TIA Portal %Q<start address + 1>.6); as input input byte 3, bit 6 (derived), 2 bytes higher in the alarm version.
2Channel 0E0.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 0E0.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
1Channel 0F0.3–1.5Configurable channel 0F (DI or DO, PNP), set via DIP switches 1–5 or automatically from the wiring. As output max. 0.5 A. PROFINET: as output output byte 1, bit 7 (in TIA Portal %Q<start address + 1>.7); as input input byte 3, bit 7 (derived), 2 bytes higher in the alarm version.
2Channel 0F0.3–1.5+24 V for the sensor of this channel, internally connected to IO+ (supply terminal 2/3).
3Channel 0F0.3–1.50 V for the sensor or load of this channel, internally connected to IO− (supply terminal 4/5).
LED––Top line: system indicators. Below, one green LED per channel: middle line = upper terminal row (channels 00–0F), bottom line = lower terminal row (channels 00–0F).
DIP––Six switches, position 0 or 1. After every change, switch the module off and on again; only then does the new setting apply (manual ch. 4.3).

* Clamping range not stated in the manual, derived.

PROFINET: GSDML, device name and channel addresses

This is how you integrate the PN5R into your controller: install the GSDML file matching the position of DIP switch 0, drag the module into the hardware configuration, assign the device name. Below you find all channels of your model with their address in TIA Portal.

At a glance

Factory default device name
PNIO
IP address
assigned by the controller
GSDML
V2.3, standard and alarm version per model
Cycle time
ab 1 ms
Tested in the manual
S7-1200 (CPU 1214C) with TIA Portal V17
  • All modules ship with the device name “PNIO”. Assign each module its own name.
  • The MAC address is printed on the device. When assigning, compare it with the list of accessible devices.

Assign device name (TIA Portal)

  1. Search for the module with Online access → Update accessible devices; under Online & diagnostics → Functions you can assign the IP address and name directly.
  2. Or, in the network view, right-click the connection between PLC and module and select Assign device name.
  3. Click Update list, select the module by its MAC address and click Assign name; the status must show “OK”.
  4. Compile, download to the PLC and switch the module off and on once.

Which GSDML file?

The ZIP under Downloads contains a standard version and an alarm version for each model. The alarm version also delivers an alarm code in the first two input bytes, so all inputs shift 2 bytes higher. DIP switch 0 on the module determines which one you need: 0 = standard, 1 = alarm. Install via Options → Manage general station description files (GSD); in the hardware catalog under Other field devices → PROFINET IO → I/O → SOLIDOT → SOLIDOT PN5 SERIES. With “Online → Hardware detection → PROFINET devices from network”, TIA Portal also finds the module by itself.

PN5R-1616B+ · 16 DI PNP / 16 DI/O PNP

Top row = channels 00–0F, bottom row = channels 00–0F. Three terminals per channel: 1 signal, 2 24 V (NC on outputs), 3 0 V. The input addresses of the configurable channels (byte 2–3, alarm version byte 4–5) are derived from the data length in the GSDML.

GSDML fileInputsOutputs
GSDML-V2.3-sdot-PN5R-1616B+-20260224.xml4 byte(s)2 byte(s)
GSDML-V2.3-sdot-PN5R-1616B+-Alarm-20260224.xml6 byte(s)2 byte(s)
Start address from the Device overview in TIA PortalGSDML version (DIP 0)

Digital inputs X00–X0F

TerminalSignalByte · BitAddress in TIA Portal
top · channel 00 · term. 1X000 · 0%I0.0
top · channel 01 · term. 1X010 · 1%I0.1
top · channel 02 · term. 1X020 · 2%I0.2
top · channel 03 · term. 1X030 · 3%I0.3
top · channel 04 · term. 1X040 · 4%I0.4
top · channel 05 · term. 1X050 · 5%I0.5
top · channel 06 · term. 1X060 · 6%I0.6
top · channel 07 · term. 1X070 · 7%I0.7
top · channel 08 · term. 1X081 · 0%I1.0
top · channel 09 · term. 1X091 · 1%I1.1
top · channel 0A · term. 1X0A1 · 2%I1.2
top · channel 0B · term. 1X0B1 · 3%I1.3
top · channel 0C · term. 1X0C1 · 4%I1.4
top · channel 0D · term. 1X0D1 · 5%I1.5
top · channel 0E · term. 1X0E1 · 6%I1.6
top · channel 0F · term. 1X0F1 · 7%I1.7

Show wiring “PNP sensors”

Configurable channels DI/O 00–0F as output

TerminalChannelByte · BitAddress in TIA Portal
bottom · channel 00 · term. 1DI/O 000 · 0%Q0.0
bottom · channel 01 · term. 1DI/O 010 · 1%Q0.1
bottom · channel 02 · term. 1DI/O 020 · 2%Q0.2
bottom · channel 03 · term. 1DI/O 030 · 3%Q0.3
bottom · channel 04 · term. 1DI/O 040 · 4%Q0.4
bottom · channel 05 · term. 1DI/O 050 · 5%Q0.5
bottom · channel 06 · term. 1DI/O 060 · 6%Q0.6
bottom · channel 07 · term. 1DI/O 070 · 7%Q0.7
bottom · channel 08 · term. 1DI/O 081 · 0%Q1.0
bottom · channel 09 · term. 1DI/O 091 · 1%Q1.1
bottom · channel 0A · term. 1DI/O 0A1 · 2%Q1.2
bottom · channel 0B · term. 1DI/O 0B1 · 3%Q1.3
bottom · channel 0C · term. 1DI/O 0C1 · 4%Q1.4
bottom · channel 0D · term. 1DI/O 0D1 · 5%Q1.5
bottom · channel 0E · term. 1DI/O 0E1 · 6%Q1.6
bottom · channel 0F · term. 1DI/O 0F1 · 7%Q1.7

Show wiring “Valve and lamp on DO”

Configurable channels DI/O 00–0F as input

TerminalChannelByte · BitAddress in TIA Portal
bottom · channel 00 · term. 1DI/O 002 · 0%I2.0
bottom · channel 01 · term. 1DI/O 012 · 1%I2.1
bottom · channel 02 · term. 1DI/O 022 · 2%I2.2
bottom · channel 03 · term. 1DI/O 032 · 3%I2.3
bottom · channel 04 · term. 1DI/O 042 · 4%I2.4
bottom · channel 05 · term. 1DI/O 052 · 5%I2.5
bottom · channel 06 · term. 1DI/O 062 · 6%I2.6
bottom · channel 07 · term. 1DI/O 072 · 7%I2.7
bottom · channel 08 · term. 1DI/O 083 · 0%I3.0
bottom · channel 09 · term. 1DI/O 093 · 1%I3.1
bottom · channel 0A · term. 1DI/O 0A3 · 2%I3.2
bottom · channel 0B · term. 1DI/O 0B3 · 3%I3.3
bottom · channel 0C · term. 1DI/O 0C3 · 4%I3.4
bottom · channel 0D · term. 1DI/O 0D3 · 5%I3.5
bottom · channel 0E · term. 1DI/O 0E3 · 6%I3.6
bottom · channel 0F · term. 1DI/O 0F3 · 7%I3.7

Module properties

Parameter (TIA Portal)DefaultMeaning
Protocol Alarm Switch0 = onPROFINET alarms on (factory default), 1 = off
DI FilterTime3 msInput filter for the whole module: off, 0.1 / 0.2 / 0.5 ms, 1–20 ms (factory default 3 ms)
DO Template Mode1 = PresetLowOutputs outside OP (loss of connection, stop): 1 = 0, 2 = 1, 3 = hold last value (factory default 1)
DO Channel n0 = TemplateValueper channel deviating 1/2/3 as above; 0 = Template Mode applies (factory default)

DIP switch “Function”

After every change, switch the module off and on again (manual chap. 4.3).

SwitchPosition 0Position 1applies to
0Standard versionAlarm version (alarm code in the input data)all models
1DI/DO of the configurable channels via DIP 2–5DI/DO automatically from the wiringPN5R-1616B+
2Channels 00–03 outputChannels 00–03 inputPN5R-1616B+, if DIP 1 = 0
3Channels 04–07 outputChannels 04–07 inputPN5R-1616B+, if DIP 1 = 0
4Channels 08–0B outputChannels 08–0B inputPN5R-1616B+, if DIP 1 = 0
5Channels 0C–0F outputChannels 0C–0F inputPN5R-1616B+, if DIP 1 = 0

On the other models, switches 1–5 have no effect. The manual does not state the factory setting of the switches.

Alarm codes

In the alarm version, the code is in the input data; TIA Portal shows the protocol alarms in the device diagnostics (wrench icon at the device in the project tree).

Code in the dataPROFINET alarmMeaning
0x0000–no error
0x00010x00C5Load voltage (field supply) not connected
0x00020x1040Digital output fault
0x00100x1041Parameter set incorrectly
0x00200x1042Channel automatically detected as input, but the corresponding output address is set

The alarm code is in the first two input bytes, the channels follow from byte 2. Measured on the PN5R-1616B alarm version (26.08.2026); the GSDML label “2DI + 2Alarm” suggests the reverse order.

If it does not work

ProblemCheck
Module does not appear in the hardware catalogGSDML installed? Version (standard/alarm) matching DIP 0?
BF flashingNo PROFINET connection to the controller yet: device name assigned and configuration downloaded?
SF on, alarm 0x00C5 / code 0x0001Field supply at terminal 3/4 (IO+/IO−) is missing.
Configurable channel does not switchCheck DIP 1–5: group set as output? Then restart.
For specialists
ItemValue
Vendor ID0x0528
Input filterper module, not per channel; max. input frequency 150 Hz at 3 ms
Response timeInput 150 µs, output < 250 µs (PNP outputs; manual ch. 3)
Module propertiesParameter data record 1 (GSDML); after changing, download and switch the module off and on again
ProtectionShort-circuit and reverse polarity protection with automatic recovery, overvoltage protection on the field side (chap. 3.1)
  • Bit n of a byte = channel n, byte 0 = channels 00–07, byte 1 = channels 08–0F (channel 00 = byte 0, bit 0 measured on the PN5R-1616B; the other channels derived from the data length in the GSDML).
  • TIA Portal assigns the start addresses automatically; you find and change them in the Device overview of the module.

Source: PN5R Series Integrated I/O User Manual V1.01 (07/2026), chap. 3, 4.2, 4.3, 7; GSDML V2.3 (Solidot, 24.02.2026).

First steps with the Solidot PN5R

The PN5R brings 32 digital channels onto PROFINET: three spring-cage terminals per channel for signal, 24 V and 0 V, two RJ45 ports with a built-in switch, diagnostics and alarms. This guide applies to the PN5R-3200, -1616B, -1616B+ and -0032B. It takes you from mounting to the first signal in TIA Portal: power supply, wiring, DIP switches, GSDML, device name, downloading and testing.

Before connecting
  • Mount and remove only with the power off (manual chap. 5.1).

  • Protection class IP20: the module belongs in a control cabinet.

  • Set up the system supply (terminal 0/1) and the field supply (terminal 3/4) separately and do not mix them.

  • Ground PE at terminal 7 securely. Use copper wires only, rated for 80 °C (manual chap. 6).

  1. 1Mounting: DIN rail or wallRequired

    The module measures 182 × 57 × 34 mm including mounting ears (housing 160 mm wide) and sits vertically – leave at least 50 mm of space above and below the module.

    On the DIN rail: pull the clip at the bottom of the back outwards, hook the module on at the top, press it onto the rail and push the clip up until it clicks.

    On the wall: push the mounting ears on the left and right outwards until they click into place, and screw the module on through the holes (⌀ 4.3 mm, spacing 169 mm). You find the drilling template in the “Dimensions & mounting” tab.

    Source: Manual chap. 3.1, 5

  2. 2Connect system and field supplyRequired

    The 8-pole connector at the top left carries both supplies: system supply 24 V DC to terminal 0 (24V) and 1 (0V), field supply to terminal 3 (IO+) and 4 (IO−). Terminals 2 and 5 are the second terminal of IO+ and IO− respectively, terminal 7 is PE.

    The field supply powers all inputs and outputs: the 24 V and 0 V terminals of each channel are connected internally to IO+ and IO−. Permissible range is 20.4–28.8 V, max. 8 A per group.

    Supply connector

    TerminalMarkingFunction
    024VSystem supply +24 V
    10VSystem supply 0 V
    2, 3IO+Field supply +24 V
    4, 5IO−Field supply 0 V
    6COM or NCInput reference on PN5R-3200 and -1616B, otherwise not used
    7PEEarth

    The supply terminals only take 0.2–0.75 mm². With a high output load (up to 6 A per 16 channels), plan the cross-section and fusing accordingly – the manual gives no recommendation for this.

    If the field supply is missing, the module reports the alarm “Load voltage not connected”.

    Show wiring “System supply 24 V”Show wiring “Field supply 24 V”

    Source: Manual chap. 3.2–3.4, 6.1, 6.3

  3. 3Connect sensors and loadsRequired

    Each channel has three spring-cage terminals one above the other: 1 signal, 2 24 V (NC on pure outputs), 3 0 V. This way a 3-wire sensor connects entirely to its own channel: BK to 1, BN to 2, BU to 3. A load goes between 1 and 3.

    Strip 9–10 mm of insulation, press the button with a flat-blade screwdriver up to 3 mm wide and insert the wire. Cross-section 0.3–1.5 mm².

    PN5R-3200 and -1616B: the inputs are NPN/PNP compatible, the reference is COM (supply terminal 6). For PNP sensors connect COM to 0 V, for NPN sensors to +24 V. PN5R-1616B+: inputs PNP only.

    Outputs: PNP, max. 0.5 A per channel, short-circuit proof with automatic recovery. Load resistive, inductive or lamp.

    Show wiring “PNP sensors”Show wiring “NPN sensors”Show wiring “Valve and lamp on DO”Show wiring “Sensors on DI/O”

    Source: Manual chap. 3.2–3.4, 6.1–6.3

  4. 4Set the DIP switchesRequired

    DIP switch 0 determines which GSDML version you need: 0 = standard, 1 = alarm version with alarm code in the input data.

    PN5R-1616B+ only: DIP 1 = 0 means DIP 2–5 each set four channels of the bottom row as input or output (0 = output, 1 = input). DIP 1 = 1 means the module detects from the wiring itself whether a channel is an input or an output.

    After every change, switch the module off and on again.

    The manual does not state the factory setting of the switches – check them before switching on for the first time.

    DIP table in the PROFINET tab

    Source: Manual chap. 4.3

  5. 5Install the GSDML fileRequired

    The ZIP under Downloads contains a standard version and an alarm version for each model. Use the one that matches DIP switch 0.

    Install

    1. Unzip the ZIP file.

    2. In TIA Portal, open Options → Manage general station description files (GSD) and select the folder as the source path.

    3. Select the file with the status “Not installed” and click Install.

    GSDML file for my model

    Source: Manual chap. 7.3.1, step 5

  6. 6Find, name and add the moduleRequired

    The manual shows the integration with an S7-1200 (CPU 1214C) and TIA Portal V17. The PC must be in the same network as the PLC.

    In TIA Portal

    1. Create a project and insert the PLC under Add new device.

    2. Online access → Update accessible devices. Under Online & diagnostics → Functions of the module, you can assign the IP address and PROFINET device name directly.

    3. In Devices & networks, select the PLC and choose Online → Hardware detection → PROFINET devices from network; apply the module found with Add new device. Alternatively from the hardware catalog: Other field devices → PROFINET IO → I/O → SOLIDOT → SOLIDOT PN5 SERIES.

    4. Click “Not assigned” on the module and select the PROFINET interface of the PLC.

    5. Right-click the connection → Assign device name, Update list, Assign name, check the status “OK”; compare the MAC address on the device.

    Show wiring “PROFINET to the controller”

    Source: Manual chap. 7.3.1, steps 2–9

  7. 7Download and testRequired

    Select the PLC, compile and Download to device, then switch the module off and on once. Start the CPU, Go online – if all symbols are green, the connection is running.

    The Device overview shows the I and Q addresses of the module (in the manual example for the 1616B+ alarm version I 2–7 and Q 2–3). In a watch table you see the inputs and write the outputs.

    Channel addresses for my model

    Source: Manual chap. 7.3.1, steps 10–13

  8. 8Set module propertiesOptional

    Offline, select the module in the device view, Properties → module properties. Then download again and switch the PLC and module off and on again.

    ParameterValueMeaning
    DI FilterTime3 msInput filter for the whole module, off up to 20 ms (factory default)
    DO Template Mode1 = PresetLowOutputs off on loss of connection or stop (factory default); 2 = on, 3 = hold last value
    DO Channel n0per channel deviating 1/2/3; 0 = Template Mode applies (factory default)
    Protocol Alarm Switch0 = onPROFINET alarms on (factory default)

    The filter applies to all inputs of the module together, not per channel. At 3 ms, the maximum input frequency is 150 Hz.

    Source: Manual chap. 7.1; GSDML (factory defaults)

  9. 9More devices in a lineOptional

    X1 and X2 are connected to the built-in switch: X2 leads to the next PROFINET device, no external switch is needed. Max. 100 m per segment.

    Each device needs its own device name.

    If a device has no power, you can no longer reach the devices behind it (derived from the built-in switch; the manual does not mention a bypass).

    Show wiring “Further device in daisy chain”

    Solidot patch cable 0.5 m

    Source: Manual chap. 3.1

  10. 10TroubleshootingRequired

    LEDs

    LEDStateMeaning
    PWR (green)offno supply or faulty supply
    RUN (green)flashingMain controller failed to start
    RUN (green)offDevice does not start
    SF (red)onPROFINET alarm active
    BF (red)onno network connection
    BF (red)flashingno PROFINET connection to the controller
    MT (yellow)onMaintenance required, alarm generated
    L/A0, L/A1 (green)offno network connection at X1 or X2 respectively

    TIA Portal shows alarm details at the wrench icon next to the device in the project tree. The alarm codes are in the PROFINET tab.

    Source: Manual chap. 4.2, 7.2

Revision 1.0 · 02.10.2026 · Source: PN5R Series Integrated I/O User Manual V1.01 (07/2026); GSDML V2.3 (Solidot, 24.02.2026). Menu names as in the English TIA Portal UI shown in the manual.. The manufacturer manual and applicable standards take precedence; installation and commissioning by a qualified electrician only.

Dimensions and mounting

All PN5R models have the same housing. It snaps onto a 35 mm DIN rail or is screwed to the wall via two mounting ears. The drawing is projected from Solidot's 3D model.

Connectors and wires

Supply (top left)

Type
8-pin, spring-clamp: 0 24V, 1 0V system · 2/3 IO+, 4/5 IO− field · 6 COM or NC · 7 PE; 300 V, 7 A
Cross-section
0.2–0.75 mm² (28–18 AWG)
Strip length
8–10 mm

Signals (2 rows of 16 channels)

Type
3 spring terminals per channel (1 signal, 2 24 V or NC, 3 0 V), 32 × 3P; 300 V, 8 A
Cross-section
0.3–1.5 mm² (22–16 AWG)
Strip length
9–10 mm

PROFINET X1/X2 (left)

Type
2 × RJ45 for PROFINET cables or patch cables Cat. 5 or higher, shielded (STP), max. 100 m

Wire ferrules with plastic collar, sleeve length 8–10 mm: E0308/E0310 (0.3 mm²), E0508/E0510 (0.5), E7508/E7510 (0.75), E1008/E1010 (1.0), E1508/E1510 (1.5 mm², signal terminals only). Solid wires without ferrule, stranded wires also without ferrule.

Copper wires only, temperature rating of the wire 80 °C (manual ch. 6.2).

Tools: flat-blade screwdriver up to 3 mm to open the spring terminals.

The manual does not state the pitch or connector dimensions.

Mounting step by step

  1. 1Choose the installation site

    Protection class IP20: the module belongs in a control cabinet. Ventilate well and do not mount it next to or above devices that give off a lot of heat.

    At least 50 mm of clearance above and below the module (manual ch. 5.1). Operating temperature −20 to +60 °C, up to 2000 m altitude.

    Show clearances in the drawing

  2. 2Mount on the DIN rail
    • Pull the clip at the bottom of the rear side outwards until it clicks into place.

    • Hook the top edge of the module's rail slot onto the top edge of the DIN rail and press the module onto the rail.

    • Push the clip upwards until it clicks.

    • Removing: insert a flat-blade screwdriver into the clip, lever it towards the module, remove the module.

  3. 3Screwing to the wall

    The manual does not state the screw size; the hole is ⌀ 4.3 mm.

    • Slide the mounting ears on the left and right of the rear side outwards until they click into place.

    • Mark the holes with the template and a spirit level: two holes, spacing 169 mm.

    • Place the module and screw it on through the mounting ears so that it does not wobble.

    Show drilling pattern in the drawing

  4. 4Connecting the wires

    Strip 8–10 mm for the supply terminals, 9–10 mm for the signal terminals. Press the push button with a flat-blade screwdriver up to 3 mm, insert the wire.

    Each channel has its own 24 V and 0 V terminal: 3-wire sensors and loads connect directly to their channel.

    Show wiring “System supply 24 V”Show wiring “PNP sensors”

Revision 1.0 · 02.10.2026 · Source: PN5R Series Integrated I/O User Manual V1.01 (07/2026), ch. 5 and 6.1; Solidot 3D model XX5-top_asm (EC5R & PN5R V1.1). The manufacturer manual and applicable standards take precedence; installation by a qualified electrician only.

Stuck?

Our support helps you free of charge. Tell us what you are planning and which model you use – via the contact form, by email or in the community forum.

More ways to contact us: Support contacts

We have compiled and checked this page carefully from the manufacturer’s documentation. Even so, an error may have slipped in. The manufacturer’s manual and the applicable standards always take precedence. Spotted something? Let us know – we’ll be glad to fix it.

Downloads

User manual, GSDML files, 2D and 3D drawings (also with dust cover) and EPLAN macros:

Solidot PN5R
User manual, GSDML files and 2D and 3D drawings for the Solidot PN5R series

Solidot PN5R remote I/O

Solidot PN5R – PROFINET Remote-I/O (Digitalmodul)
If you want to connect sensors and actuators to a PROFINET controller in a decentralised way – without running every single wire all the way back to the main cabinet – the Solidot PN5R series offers a compact, low-profile PROFINET remote I/O system. The modules sit where the signals originate – on the machine or in the field distributor – and transmit all inputs and outputs to the controller over a single Ethernet cable. Every channel has three dedicated terminals: signal, 24 V and 0 V. Sensors and actuators are therefore powered directly at the module, with no separate distribution terminals. Status LEDs right next to each channel show every input and output directly at the terminal point. 🏭 Typical applications Decentralised machine modules: Each assembly gets its own I/O module, connected via the PROFINET line – new modules are simply added in series. Relieve the control cabinet: Instead of hundreds of wires to the central cabinet, only two RJ45 cables run per module. Fewer cable ducts, fewer terminals, a clearer system. Sensor wiring without a distribution level: Because 24 V and 0 V are carried on every channel, a three-wire sensor goes straight onto the module – no additional potential distribution, no jumper combs. Retrofit on Siemens controllers: Extend existing S7-1200 or S7-1500 installations with decentralised I/O without enlarging the central PLC. Mixed signal direction: From a pure 32-channel input or output module to the 16/16 combination – on the 1616B+ model, 16 channels are freely configurable as inputs or outputs. So one variant still fits even when requirements change. 🌐 PROFINET: one cable for all signals The PN5R modules are standard-compliant PROFINET slaves and are imported into the project via their GSDML device description file. Each module has two RJ45 ports (100 Mbps) and is daisy-chained – no additional switch required. The minimum cycle time between controller and module is 1 ms, the input reaction time 150 µs. 🔗 Compatibility As a standard PROFINET device, the PN5R series works with controllers from various manufacturers; the manual documents configuration in TIA Portal V17. The inputs of the 3200 and 1616B types accept either NPN or PNP sensors – handy when both sensor types exist in your installed base. 🔌 Design and connection 3 terminals per channel: Signal, 24 V and 0 V are available on every channel – sensor and actuator supply is integrated in the module. That saves the entire supply distribution in the cabinet. Tool-free spring terminals: Power supply (8-pole) and I/O are connected via push-in spring terminals – insert the conductor, done, no screwdriver needed. Mounting: 35 mm DIN rail or direct wall mounting via the side fixing ears. Compact low-profile housing (182 × 58 × 34 mm), passive cooling – no fan, no maintenance. Power supply: 24 V DC, permissible 20.4 – 28.8 V DC, max. 8 A per terminal group on the field side. Green status LED per channel, right at the terminal. ⚙️ Configurable without extra software DIP switch on the device: The alarm version and – on the configurable models – the direction of the I/O channels are set directly on the module. Input filter 0 to 20 ms: Adjustable per module via PROFINET (factory setting 3 ms) – bouncing contacts can be settled without PLC code. Clear/hold on bus failure: Outputs can be configured module-wide or per channel to "clear", "set to 1" or "hold last value". Diagnostics: Short-circuit and reverse-polarity protection with automatic recovery, wire-break and alarm messages via PROFINET, firmware update supported. ⚠️ Limits stated honestly Protection rating IP20 – for control cabinets or protected enclosures, not for the unprotected field environment. Power supply exclusively 20.4 – 28.8 V DC, no AC supply. Operation from -20 °C to +60 °C (passive cooling). Standard process I/O – no functional-safety (safety) inputs/outputs. A separate safety controller is required for emergency stop and similar functions. PN5R modules are slave devices and require a PROFINET controller – they do not replace a PLC. The input filter applies per module, not per channel. 🏷️ Manufacturer and reliability Solidot (s'Dot) specialises in industrial networking and remote I/O technology. The PN5R modules are CE- and RoHS-compliant and built for industrial use; inputs and outputs are galvanically isolated (500 V AC) and the transistor outputs are short-circuit proof with automatic recovery. Tested to IEC 60068-2-6 (vibration) and IEC 60068-2-27 (shock). spstiger offers the series with German-language advice and support.
Variants from €150.00 *
€187.50 *

Preis exkl. MwSt., zzgl. Versandkosten

Accessories

Solidot Patchkabel RJ45/RJ45 – geschirmt, grün
Assembled, shielded Ethernet cables for the fieldbus wiring of Solidot remote I/O modules — RJ45 on both ends, green jacket per industry convention. Available in seven lengths from 0.5 to 20 m and two jacket materials. 🔌 What for Connection between PLC and remote I/O module, and for daisy-chaining module to module (2 × RJ45 per module, no switch required). Protocol-neutral: PROFINET (PN4, PN5R, PN7A), EtherCAT (EC4, EC5R, EC7A), EtherNet/IP (EI4) and Modbus TCP (MT4). 🧵 PVC or PUR — which one PVC: the more economical choice for fixed installation in the cabinet and in cable ducts. PUR: tougher, more abrasion-resistant and oil-resistant — for moving installation, machine environments and anything that does not just sit in the cabinet. 📐 Technical basis CAT 5e, shielded, 100 Mbps — matching the Ethernet interface of the Solidot modules. Maximum cable length between two stations: 100 m (fieldbus specification). Lengths: 0.5 · 1 · 2 · 3 · 5 · 10 · 20 m. Custom lengths are available from the manufacturer on request — get in touch if you need one. ⚠️ Limits stated honestly RJ45 is an IP20 connector — for control cabinets and protected enclosures. In the field with splash water or dust, M12 cables (D-coded) are the right choice. CAT 5e, not CAT 6/CAT 6a. Not meant for gigabit backbones — the Solidot modules operate at 100 Mbps anyway.