Filter
–
Two serial ports are not enough because an inverter, a barcode scanner and a scale all need to be connected? The KB6-2COM adds an RS-232 (port 0) and another RS-485 (port 3) to the K6. It plugs into BD slot BD0.
🔌 Interfaces
RS-232 (port 0): Modbus RTU slave, free protocol and programming, for example for scanners, printers or an older panel.
RS-485 (port 3): Modbus RTU master or slave and programming.
Baud rate: 1200 to 115 200 bit/s.
Connection: shared DB9 connector. RS-232 on pins 2 (RxD), 3 (TxD) and 5 (GND), RS-485 on pins 1 (B) and 6 (A).
💡 On the K606EA and K608, only BD0 accepts communication boards.
🔧 Mounting and environment
The board plugs directly onto the CPU, needs no space on the DIN rail and no separate supply. A LINK LED indicates that it is seated correctly.
- Available
- Delivery Time : 2-5 days
You only need a few more inputs and a whole expansion module would be overkill? The KB6-4DI plugs directly onto the K6 CPU and adds four digital inputs. It fits any BD slot, so on the K606EA and K608 also BD1.
⚡ Inputs
4 digital inputs 24 V DC, wired as PNP or NPN.
Input current 3.5 mA at 24 V DC, input delay below 40 µs.
Optocoupler isolation with 500 V AC.
Connection via terminal block with 3.81 mm pitch.
🔧 Mounting and environment
The board plugs directly onto the CPU, needs no space on the DIN rail and no separate supply. A LINK LED indicates that it is seated correctly.
- Available
- Delivery Time : 2-5 days
Two signal lamps and a valve don't justify a whole output module? The KB6-4DO plugs directly onto the K6 CPU and adds four outputs. It fits any BD slot, so on the K606EA and K608 also BD1.
⚡ Outputs
4 opto-relay outputs 24 V DC (permissible 20.4 V to 28.8 V DC), wired as PNP or NPN via the common terminal L.
Output current 300 mA rated, max. 500 mA per channel, short-circuit proof and protected against switch-off peaks of inductive loads.
Switching delay below 10 ms. For fast pulses, use the CPU's transistor outputs.
Optocoupler isolation with 500 V AC.
Connection via terminal block with 3.81 mm pitch.
🔧 Mounting and environment
The board plugs directly onto the CPU, needs no space on the DIN rail and no separate supply. A LINK LED indicates that it is seated correctly.
- Available
- Delivery Time : 2-5 days
Your K6 has more expansion modules than its own bus supply can carry? The K680 (also PS680) feeds fresh 5 V and 24 V into the expansion bus. All modules after the K680 are powered by it, all modules before it by the CPU.
⚡ Technical data
Input: 85 to 265 V AC.
Output to the bus: up to 1000 mA at 5 V (logic supply) and up to 250 mA at 24 V (relay drive).
Plug & play: uses no CPU memory and does not need to be configured in KincoBuilder.
Status indication: PW LED.
💡 How to plan the current budget
The K6 CPU provides 1500 mA at 5 V and 360 mA at 24 V. Add up the bus consumption of your modules, for example 210 mA for a K621-16DX, or 210 mA and 120 mA for a K622-16XR. When the budget gets tight, you place the K680 at the right position in the module row. Kinco generally recommends it from 7 expansion modules. Make sure the K680 and the CPU are fed from the same supply.
🔧 Mounting and environment
Protection class IP20, operation from −10 °C to +55 °C, CE marked. Mounting on 35 mm DIN rail or with M4 screws, connection via screw terminals.
Dimensions 75 mm × 114 mm × 70 mm (W × H × D).
- Available
- Delivery Time : 2-5 days
You want to connect servo drives, stepper drivers or CANopen I/O to your K6 without adding a gateway to the cabinet? The KB6-CAN adds a CAN interface to the CPU. It plugs into BD slot BD0.
🌐 Functions
CANopen master: up to 64 slaves with 8 TPDO and 8 RPDO each, error monitoring via node guarding and heartbeat.
Kinco motion protocol: simple positioning instructions for up to 16 Kinco servo and stepper drives on the CAN bus.
Free CAN communication for your own telegrams.
Baud rates: 10, 20, 50, 125, 500 and 800 kbit/s as well as 1 Mbit/s.
Connection: RJ45 (pin 1 CAN_H, pin 2 CAN_L, pin 3 CAN_GND), built-in termination resistor switchable via DIP switch.
💡 On the K606EA and K608, only BD0 accepts communication boards; BD1 is reserved for I/O boards.
🔧 Mounting and environment
The board plugs directly onto the CPU, needs no space on the DIN rail and no separate supply. A LINK LED indicates that it is seated correctly.
- Available
- Delivery Time : 2-5 days
You are missing a few inputs and outputs, for example for an additional cylinder with end position sensors? The slim K623-08DT adds 4 inputs and 4 transistor outputs to your Kinco K6.
⚡ Technical data
4 digital inputs 24 V DC, wired as PNP or NPN, 3.5 mA input current, optically isolated.
4 transistor outputs PNP, 500 mA per channel at 24 V DC, protected against short circuit, inductive loads and reverse polarity.
Output delay below 25 µs.
Status indication via green LED per channel.
Power comes via the expansion bus: the module draws up to 200 mA at 5 V. A K6 CPU provides a total of 1500 mA at 5 V and 360 mA at 24 V. If the budget is not enough for your module row, you insert the K680 power supply.
🔧 Mounting and environment
Protection class IP20, operation from −10 °C to +55 °C, CE marked. Mounting on 35 mm DIN rail or with M4 screws, connection via screw terminals.
Dimensions 50 mm × 114 mm × 70 mm (W × H × D).
- Available
- Delivery Time : 3-4 weeks
Limit switches, light barriers and push buttons have used up your CPU inputs? The K521-16DX expands your Kinco controller with 16 digital inputs.
⚡ Technical data
16 digital inputs in 2 groups of 8 channels, 24 V DC, wired as PNP or NPN, 3.5 mA input current, optically isolated.
Input delay below 40 µs.
Status indication via green LED per channel.
Power comes via the expansion bus: the module draws up to 210 mA at 5 V. A K6 CPU provides a total of 1500 mA at 5 V and 360 mA at 24 V. If the budget is not enough for your module row, you insert the K680 power supply.
💡 Expansion module of the Kinco K5 series. It works with K5 CPUs and directly with all K6 CPUs (K606, K606EA, K608), whose expansion bus is compatible with the K5. Technically it corresponds to the K6 module K621-16DX.
🔧 Mounting and environment
Protection class IP20, operation from −10 °C to +55 °C, CE marked. Mounting on 35 mm DIN rail or with M4 screws, connection via screw terminals.
- Available
- Delivery Time : 2-5 days
You need more inputs for sensors and potential-free contacts for 230 V loads at the same time? The K623-16DR adds 8 inputs and 8 relay outputs to your Kinco K6 in one module.
⚡ Technical data
8 digital inputs 24 V DC, wired as PNP or NPN, 3.5 mA input current, optically isolated.
8 relay outputs in 2 groups of 4 channels.
Switching capacity: 2 A per contact at 30 V DC or 250 V AC, max. 8 A per group of 4 channels. Electrical life 100 000 operations at rated load, coil/contact isolation 2000 V.
Status indication via green LED per channel.
Power comes via the expansion bus: the module draws up to 210 mA at 5 V and 60 mA at 24 V. A K6 CPU provides a total of 1500 mA at 5 V and 360 mA at 24 V. If the budget is not enough for your module row, you insert the K680 power supply.
🔧 Mounting and environment
Protection class IP20, operation from −10 °C to +55 °C, CE marked. Mounting on 35 mm DIN rail or with M4 screws, connection via screw terminals.
Dimensions 75 mm × 114 mm × 70 mm (W × H × D).
- Available
- Delivery Time : 2-5 days
You want to connect a machine station with sensors and valves in one go? The K523-16DT adds 8 inputs and 8 transistor outputs to your Kinco controller.
⚡ Technical data
8 digital inputs 24 V DC, wired as PNP or NPN, 3.5 mA input current, optically isolated.
8 transistor outputs in 2 groups of 4 channels, PNP, 500 mA per channel at 24 V DC, protected against short circuit, inductive loads and reverse polarity.
Status indication via green LED per channel.
Power comes via the expansion bus: the module draws up to None mA at 5 V. A K6 CPU provides a total of 1500 mA at 5 V and 360 mA at 24 V. If the budget is not enough for your module row, you insert the K680 power supply.
💡 Expansion module of the Kinco K5 series. It works with K5 CPUs and directly with all K6 CPUs (K606, K606EA, K608), whose expansion bus is compatible with the K5. Technically it corresponds to the K6 module K623-16DT.
🔧 Mounting and environment
Protection class IP20, operation from −10 °C to +55 °C, CE marked. Mounting on 35 mm DIN rail or with M4 screws, connection via screw terminals.
- Available
- Delivery Time : 2-5 days
You need to switch contactors, solenoid valves or 230 V AC loads and the CPU outputs are not enough? The K622-16XR expands your Kinco K6 with 16 potential-free relay outputs.
⚡ Technical data
16 relay outputs in 4 groups of 4 channels.
Switching capacity: 2 A per contact at 30 V DC or 250 V AC, max. 8 A per group of 4 channels. Electrical life 100 000 operations at rated load, coil/contact isolation 2000 V.
Switching times: turn-on max. 10 ms, turn-off max. 5 ms.
Status indication via green LED per channel.
Power comes via the expansion bus: the module draws up to 210 mA at 5 V and 120 mA at 24 V. A K6 CPU provides a total of 1500 mA at 5 V and 360 mA at 24 V. If the budget is not enough for your module row, you insert the K680 power supply.
🔧 Mounting and environment
Protection class IP20, operation from −10 °C to +55 °C, CE marked. Mounting on 35 mm DIN rail or with M4 screws, connection via screw terminals.
Dimensions 75 mm × 114 mm × 70 mm (W × H × D).
- Available
- Delivery Time : 2-5 days
Valve terminals, signal lamps and auxiliary contactors need more outputs than your CPU has? The K522-16DT expands your Kinco controller with 16 transistor outputs.
⚡ Technical data
16 transistor outputs in 4 groups of 4 channels, PNP, 500 mA per channel at 24 V DC, protected against short circuit, inductive loads and reverse polarity.
Output delay below 25 µs.
Status indication via green LED per channel.
Power comes via the expansion bus: the module draws up to 240 mA at 5 V. A K6 CPU provides a total of 1500 mA at 5 V and 360 mA at 24 V. If the budget is not enough for your module row, you insert the K680 power supply.
💡 Expansion module of the Kinco K5 series. It works with K5 CPUs and directly with all K6 CPUs (K606, K606EA, K608), whose expansion bus is compatible with the K5. Technically it corresponds to the K6 module K622-16DT.
🔧 Mounting and environment
Protection class IP20, operation from −10 °C to +55 °C, CE marked. Mounting on 35 mm DIN rail or with M4 screws, connection via screw terminals.
- Available
- Delivery Time : 2-5 days
Pressure, level, flow: your transmitters deliver standard signals and the CPU has no or too few analog inputs? The K531-04IV takes four current or voltage signals.
⚡ Technical data
4 analog inputs for 4 – 20 mA, 0 – 20 mA, 1 – 5 V and 0 – 10 V, selectable per channel.
Resolution 12 bit, accuracy 0.3 % of full scale, about 15 conversions per second and channel.
Input limits 24 mA or 12 V, input resistance up to 500 Ω in current mode, above 4 MΩ in voltage mode.
Diagnostics: red LED and error message to the CPU when out of range.
External supply 24 V DC, at least 100 mA.
Power comes via the expansion bus: the module draws up to 172 mA at 5 V. A K6 CPU provides a total of 1500 mA at 5 V and 360 mA at 24 V. If the budget is not enough for your module row, you insert the K680 power supply.
💡 Expansion module of the Kinco K5 series. It works with K5 CPUs and directly with all K6 CPUs (K606, K606EA, K608), whose expansion bus is compatible with the K5. Technically it corresponds to the K6 module K631-04IV.
🔧 Mounting and environment
Protection class IP20, operation from −10 °C to +55 °C, CE marked. Mounting on 35 mm DIN rail or with M4 screws, connection via screw terminals.
- Available
- Delivery Time : 2-5 days
You want to measure temperatures in an oven, cooling circuit or barn directly with resistance thermometers, without transmitters in between? The K531-04RD reads four Pt100, Pt1000 or Cu50 sensors directly.
⚡ Technical data
4 measuring channels for Pt100 (−200 °C to +850 °C), Pt1000 (−50 °C to +300 °C) and Cu50 (−50 °C to +150 °C) as well as direct resistance (0 Ω to 2000 Ω).
Connection in 2-wire or 3-wire technology.
Accuracy ±0.5 °C or ±1 Ω, resolution 24 bit, about one conversion per second and channel.
Diagnostics: red LED and error message to the CPU when out of range.
External supply 24 V DC, at least 100 mA.
Power comes via the expansion bus: the module draws up to 172 mA at 5 V. A K6 CPU provides a total of 1500 mA at 5 V and 360 mA at 24 V. If the budget is not enough for your module row, you insert the K680 power supply.
💡 Expansion module of the Kinco K5 series. It works with K5 CPUs and directly with all K6 CPUs (K606, K606EA, K608), whose expansion bus is compatible with the K5. Technically it corresponds to the K6 module K631-04RD.
🔧 Mounting and environment
Protection class IP20, operation from −10 °C to +55 °C, CE marked. Mounting on 35 mm DIN rail or with M4 screws, connection via screw terminals.
- Available
- Delivery Time : 2-5 days
Furnaces, extruders, hot runners: where resistance thermometers reach their limits, thermocouples keep measuring. The K531-04TC reads four thermocouples directly.
⚡ Technical data
4 measuring channels for thermocouples type J (−210 °C to +1200 °C), K (−270 °C to +1300 °C), E (−270 °C to +1000 °C) and S (−50 °C to +1600 °C).
Cold junction compensation internal or external, selectable.
Accuracy 0.1 % of full scale, resolution 24 bit, about one conversion per second and channel.
Diagnostics: red LED and error message to the CPU when out of range.
External supply 24 V DC, at least 100 mA.
Power comes via the expansion bus: the module draws up to 172 mA at 5 V. A K6 CPU provides a total of 1500 mA at 5 V and 360 mA at 24 V. If the budget is not enough for your module row, you insert the K680 power supply.
💡 Expansion module of the Kinco K5 series. It works with K5 CPUs and directly with all K6 CPUs (K606, K606EA, K608), whose expansion bus is compatible with the K5. Technically it corresponds to the K6 module K631-04TC.
🔧 Mounting and environment
Protection class IP20, operation from −10 °C to +55 °C, CE marked. Mounting on 35 mm DIN rail or with M4 screws, connection via screw terminals.
- Available
- Delivery Time : 2-5 days
You want to close a control loop: actual value in from the transmitter, manipulated value out to a valve or inverter? The K533-04IV provides 2 analog inputs and 2 analog outputs in one module.
⚡ Technical data
2 analog inputs for 4 – 20 mA, 0 – 20 mA, 1 – 5 V and 0 – 10 V, 12 bit, accuracy 0.3 % of full scale.
2 analog outputs for 4 – 20 mA, 0 – 20 mA, 1 – 5 V and 0 – 10 V, 12 bit, accuracy 0.3 % of full scale, load up to 500 Ω in current mode, above 1 kΩ in voltage mode.
Conversion rate about 15 per second and channel.
Diagnostics: red LED when the rated range is exceeded.
External supply 24 V DC, at least 100 mA.
Power comes via the expansion bus: the module draws up to 166 mA at 5 V. A K6 CPU provides a total of 1500 mA at 5 V and 360 mA at 24 V. If the budget is not enough for your module row, you insert the K680 power supply.
💡 Expansion module of the Kinco K5 series. It works with K5 CPUs and directly with all K6 CPUs (K606, K606EA, K608), whose expansion bus is compatible with the K5. Technically it corresponds to the K6 module K633-04IV.
🔧 Mounting and environment
Protection class IP20, operation from −10 °C to +55 °C, CE marked. Mounting on 35 mm DIN rail or with M4 screws, connection via screw terminals.
- Available